AAG skydome for protected escape route ventilation AAG skydome for protected escape route ventilation

AAG wing overview and technical data

Reaction to fire Class
Heat transfer coefficient - glazing Ut
Heat transfer coefficient - skydome without upstand Ur
Heat transfer coefficient - skydome with upstand Urc
Upward load UL
Downward load DL
Soft body impact SB
Air permeability AP
Sound transmission loss Rw
Watertightness Comply
Hard body impact Comply
Radiation properties tD65 /g
  • Dome glazing CHÚC with reaction to fire, PET-G 2 - 5 skin
    • reaction to fire according to ČSN EN 13 501-1
    • top layer - PET-G dome, clear
    • bottom layers - PET-G dome, clear
    • aluminium AAG frame thermally broken
    Reaction to fire:
    with upstand from steel = B, with upstand from PVC = E
    Heat transfer coefficient Ut/Ur/Urc (W/m2.K):
    double skin = 2,7/2,4/1,7, triple skin = 1,8/1,8/1,4, quad skin = 1,3/1,5/1,3, penta skin = 1,1/1,4/1,2 W/m2.K
    Radiation properties (tD65/g):
    double skin = 77%/0,74, triple skin = 68%/0,64, quad skin = 60%/0,55, penta skin = 53%/0,47
    UL = 3000, DL = 2500, SB = 1200, AP 6, Rw = 26 dB (quad skin)
    download technical sheets
  • Dome glazing CHÚC of protected escape route with rection to fire, PET-G/PC sheet
    • reaction to fire according to ČSN EN 13 501-1
    • top layer - double skin PET-G dome, clear
    • bottom layer - 25 mm PC sheet, clear or opal diffused
    • aluminium AAG frame thermally broken
    Reaction to fire:
    with upstand from steel = B, with upstand from PVC = E
    Heat transfer coefficient Ut/Ur/Urc = 0,87/1,2/1,1 W/m2.K
    Radiation properties (tD65/g): PC tl.25 mm, clear = 38%/0,36, opal diffused = 31%/0,31
    UL = 3000, DL = 2500, SB = 1200, AP 4, Rw = 30 dB
    download technical sheets
  • Flat glazing CHÚC with reaction to fire, insulated safety glass
    • reaction to fire according to ČSN EN 13 501-1
    • bottom layer - double skin PET-G dome, clear
    • bottom layer - insulated safety glass Iplus Advanced 6-16-VSG 44.2,1.0 - top tempered for resistance to breakage - bottom laminated safety glass
    • aluminium AAG frame thermally broken
    Reaction to fire:
    with upstand from steel = A1, with upstand from PVC = E
    Heat transfer coefficient Ut/Ur/Urc = 1,0/1,4/1,5 W/m2.K
    Radiation properties (tD65/g= 75%/0,55
    UL = 3000, DL = 2500, 1B1, AP 4, Rw = NPD

Note: AAG skydomes - Protected Escape Routes(CHÚC) are used with upstand of minimum height of 30 cm.

rez AAG kop

 

Example of quote calculation

CHÚC – skydome for ventilation of escape routes

Dimension A = B = 100x200 cm

 

 

chuc-obr-1

 

Components:

- CHÚC dome glazing with reaction to fire, PET-G/PC sheet

 

- AAG fire resistant vertical steel upstand, white, varnished with insulation, height 30cm

Description: outer and inner layer FeZn 1,5 mm sheet, colour RAL 9010, inner insulation ORSIL thickness 50 mm TF PROFI, Up=0,96 W/m2.K

 

- Skydome opener – BF 2.2-105-SG60N

Description: BF mechanism, console 2.2, motor SG60N, opening angle 105°, snow load 500N, opening time 60 s

 

Price of the set = 38 864,- CZK

 

Other accessories:

 

Switchboard, type RWZ 4.8d

Price = 15 680,- CZK

chuc-obr-2
Optical smoke sensor, type RM-O

Price = 1 983,- CZK

chuc-obr-3

 

 

 

 

 

 

 

 

 

 

 

Emergency fire button, type RT2-K-RT without indication

Price = 1 674,- CZK

Emergency fire button, type RT2-K-RT-BS with indication

Price = 2 027,- CZK

chuc-obr-4Interior switch for daily ventilation, type LT-UP

Price = 300,- CZK

chuc-obr-5

 

 

 

 

 

 

 

 

 

 

All prices exclude VAT, transport and assembly.

 

Obecné schéma zapojení CHÚC 1.pdf

Obecné schéma zapojení CHÚC 2.pdf